Commercial real estate
Commercial real estate properties are the principal users of RU-FLEX foam rubber insulation. Heating, ventilation and air-conditioning systems, cold and hot water supply systems – for each area there is a ready-made solution to increase the efficiency of buildings and structures.
Increased demands on the efficiency of heating systems require materials with modern thermal conductivity and durability. RU-FLEX foam rubber thermal insulation meets these high requirements. Maximum service life in the line of thermal insulation materials, easy mounting and inspection of thermal insulation systems are a guarantee of successful commercial real estate operation.
To help choose the right RU-FLEX ST insulation thickness, we have prepared ready-made solutions (basic calculations).
Problem and solution
- 01Minimization of heat losses into the environment
- Calculation of insulation thickness at standard heat flow density
- 02Burn protection
- Calculation of insulation thickness at a given temperature on the insulation surface.
Calculation of insulation thickness according to normative heat flux density.
Initial data
- Heat transfer medium: water
- tm = 95/70 ˚С – coolant temperature in the pipe;
- tо = 25 ˚С – temperature in the shopping center.
According to SP (Construction Regulations) 61.13330.2012 "Thermal insulation of equipment and pipelines" paragraph 6.12: it is allowed to accept the nearest lower thickness of the thermal insulation layer in cases of calculation of temperature on the insulation surface and heat flux density norms, if the difference between the calculated and nominal thickness does not exceed 3 mm.
Steel pipe diameter, mm | Operating mode (24-hour or heating period) | Design thickness of insulation, RU-FLEX ST, mm | Recommended insulation thickness, RU-FLEX ST, mm |
---|---|---|---|
89 |
> 5000 hours (209 days or more) |
40,55/32,92 | Т40/Т32 |
≤ 5000 hours (208 days or less) |
33,22/27,94 | Т32/Т25 |
Steel pipe diameter, mm | Operating mode (24-hour or heating period) | Calculated insulation thickness, RU-FLEX ST PROM ALU, mm | Recommended insulation thickness, RU-FLEX ST PROM ALU, mm |
---|---|---|---|
89 |
> 5000 hours (209 days or more) |
38,63/31,05 | Т40/Т32 |
≤ 5000 hours (208 days or less) |
31,29/26,06 | Т32/Т25 |
T-Designation of the tubular material.
Calculations made according to SP 61.13.330.2012 RF
Calculation of insulation thickness according to a given temperature on the insulation surface.
Initial data
- Heat transfer medium: water
- tm = 95/70 ˚С – coolant temperature in the pipe;
- tо = 25 ˚С – temperature in the shopping center.
According to SP (Construction Regulations) 61.13330.2012, paragraph 6.7.1: for insulated surfaces located in working or service areas of rooms and containing substances with a temperature of 150 °C or lower, the surface temperature of the thermal insulation should not exceed 40 °C.
Steel pipe diameter, mm | Insulation surface temperature not exceeding ˚C | Design thickness of insulation, RU-FLEX ST, mm | Recommended insulation thickness, RU-FLEX ST, mm |
---|---|---|---|
89 | 40 | 11,47/6,36 | Т13/Т9 |
Steel pipe diameter, mm | Insulation surface temperature not exceeding ˚C | Calculated insulation thickness, RU-FLEX ST PROM ALU, mm | Recommended insulation thickness, RU-FLEX ST PROM ALU, mm |
---|---|---|---|
89 | 40 | 16,51/9,28 | Т19/ Т13 |
The supply and return heat pipes in residential buildings have a heating medium temperature of +60 to +120 C according to SP (Construction Regulations) 61.13330.2012. To ensure efficient operation of the thermal insulation and to reduce heat loss, it is recommended to use insulation with a higher temperature range. RU-FLEX VT rubber insulation is one of the technical solutions that can work in a wide range of temperatures: from - 200 to + 150 C° (up to + 180 C° for a short time).
Calculations made according to SP 61.13.330.2012 RF